R-32 pressure temperature chart

The R-32 PT chart pairs saturation pressure with saturation temperature so you can estimate refrigerant temperature from a gauge. Use the chart with the equipment data plate and your service method, then confirm the correct target before adjusting charge.

R-32 PT table

The table below is where pressure and temperature are matched for R-32 service work. Use the pressure side to read the corresponding saturation temperature, then compare that reading with the equipment instructions and the job condition.

If you need a broader refrigerant reference, see the full PT chart index or go back to the HVAC Refrigerant Log home page.

Bubble point and dew point

For blend refrigerants, the chart method can depend on whether you are checking superheat or subcooling. R-32 guidance should be confirmed from the chart source you are using, and any glide note should be read before servicing.

For handling guidance that applies to service work, see A2L refrigerant handling.

Using the R-32 chart with gauges

Read the gauge, match it to the saturation temperature on the chart, and compare that result with the system target. Use the equipment data plate first, then verify your reading with the service method you are applying.

If you want a quick way to compare readings, use the superheat and subcooling calculator.

R-32 safety and handling notes

Before servicing, review the refrigerant handling notes for the system and the chart source. If the refrigerant is classified as an A2L, follow the handling guidance that applies to that class and recover refrigerant with the proper equipment and procedures.

More service notes are collected in the A2L refrigerant handling guide.

Compare with other refrigerants

When comparing R-32 with another refrigerant, use the matching chart for each refrigerant rather than assuming the same pressure at the same temperature. Check the data plate and chart source for the exact system you are servicing.

For another chart reference, return to the PT chart index or visit the waitlist page for the HVAC Refrigerant Log app.

Reference only. Verify with manufacturer data and gauges. Follow the manufacturer chart and EPA rules. This site is not an approval from EPA.

R-32 pressure temperature values calculated with CoolProp. Not copied from a manufacturer chart. Saturation pressure at this temperature. Reference only. Verify with manufacturer data and gauges.
Temp FSaturation psig
-2026.8
-1037.1
049.3
1063.5
2080.0
3099.1
40121.0
50145.8
60174.0
70205.8
80241.5
90281.3
100325.7
110374.9
120429.3

CoolProp is used under the MIT license. This page is not an approval from EPA.